Island Operation in Power Systems

1. Island Operation

In recent years, the generation and integration of renewable energy sources (RES) such as wind farms, PV plants, and battery energy storage systems are increased in the power systems to meet the energy demand. Due to this integration of renewable energy sources, the power electronic converters are used for power generation in most of the renewables such as type-3 and type-4 wind turbine-based generators, PV inverters, and battery energy storage systems.

Consider the power system shown in Fig. 1. Suppose, If the electrical power grid is disconnected by breaker tripping due to intentional (i.e., maintenance or permanent fault) or unintentional (i.e., blackout due to disconnection from the utility), then the power grid is isolated from the converter-based sources and loads. In such a condition, the converter-based sources only supply to the loads called an island operation. The island operation is a standalone mode of operation of a generator (which is not connected to the electrical power grid) supplying to the loads.

Fig. 1. Island Operation in Power Systems. 

2.   Problems with Island Operation

3. Islanding Detection Methods

There are two methods used for the detection of Island operation that are local and remote techniques.

3.1. Local Detection Methods

Local islanding detection methods use local measurements for island detection. It measures the system parameters such as voltage, frequency, active power, reactive power, phase angle, impedance, and harmonic distortion at the RES (locally) for island detection. Local islanding methods can be classified into two methods such as passive and active methods.

3.1.1. Passive Methods

In the passive methods, the system parameters are measured and compared with the predetermined threshold value to detect the island operation. The following system parameters can be measured.

The passive methods can be implemented with low cost, and it will not affect the power quality. Therefore, it is a widely used technique. The passive methods have a non-zero detection zone (NDZ). Fig. 2 shows the non-zero detection zone (NDZ). Here, OF – Overfrequency, UF – Underfrequency, OV – Overvoltage, and UV – Undervoltage. The island operation will not be detected if the power mismatch between RES and loads happens inside this region. Since the NDZ region is large, this method fails to detect the island operation inside this region.

Fig. 2. Non-zero detection zone (NDZ).

3.1.2. Active Methods

The active methods introduce perturbation or disturbances (i.e., inject the signal) into the frequency, voltage, and impedance parameters and observe the signals to detect the island operation.

The active methods are more popular since it provides high accuracy in the measurement. However, the active methods can affect the power quality of the grid/system since it injects a perturbation signal, and it can lead to instability.

3.2. Remote Detection Methods

The remote islanding detection methods use advanced communication infrastructure between the grid and renewable energy generation to detect the island operation.

This method is more reliable than local techniques and it will not affect the power quality. However, it is more expensive to implement.

References

Connect with us via mohanbe.m@gmail.com