HVDC Links and Configurations

The HVDC link configurations can be classified into the following categories:

1. Monopole HVDC link

2. Bipole HVDC link

1.  Monopole HVDC Link

The monopole HVDC link can be configured as symmetric monopole, asymmetric monopole with metallic return and asymmetric monopole with ground return.

1.1. Symmetric Monopole HVDC Link

The symmetric monopole HVDC link is shown in Fig. 1. In this configuration, the converters are connected to the two high-voltage conductors at opposite polarity. In symmetric monopole, the ground connection can be given at multiple points. The preferred ground connection is at the middle point of the DC link capacitors. So, the steady state voltage for each pole is half of the nominal DC voltage of the converter such as +Vdc/2, -Vdc/2, where Vdc is the nominal pole-to-pole DC voltage.

Fig. 1. Symmetric monopole HVDC link.

1.2. Asymmetric Monopole HVDC Link with Metallic Return

Fig. 2 shows the asymmetric monopole HVDC link with metallic return configuration. In normal operation, the voltage on the positive pole is the nominal DC voltage of the converter (Vdc) and the voltage on the metallic return conductor is zero. Normally only one converter is grounded because the earth current will flow when both converters are solidly grounded.

Fig. 2. Asymmetric monopole HVDC link with metallic return.

1.3. Asymmetric Monopole HVDC Link with Ground Return

Fig. 3 shows the asymmetric monopole HVDC link with ground return configuration. Since the return path is a ground return, there is only one fully insulated conductor that can reduce the cost. Also, there is a possibility of expansion to the bipole HVDC link. However, there are some environmental concerns like permission for installing the electrodes and continuous ground current.

Fig. 3. Asymmetric monopole HVDC link with ground return.

2. Bipole HVDC Link

The bipole HVDC link can configured into bipole with ground return and bipole with metallic return HVDC links. The bipole HVDC link can provide high power rating when compared to Monopole HVDC link. Each converter is connected to the AC grid via different transformer groups. One pole uses Yg-Δ and the other pole uses Yg-Y transformer configurations to reduce the harmonics on the AC side. The bipole HVDC link can be operated as monopole HVDC when there is a fault in one pole/converter.

2.1. Bipole HVDC Link with Ground Return (Symmetric Bipole)

Fig. 4. Shows the bipole HVDC link with ground return configuration. The bipole HVDC link with metallic return can be refereed as symmetric bipole configuration. This configuration uses ground return and so the ground current can be increased when both the poles are not balanced during pole outages or maintenance periods.

Fig. 4. Bipole HVDC link with ground return.

2.2. Bipole HVDC Link with Metallic Return (Asymmetric Bipole)

Fig. 5. Shows the bipole HVDC link with metallic return configuration. This configuration can be referred as asymmetric bipole configuration. In this configuration, the extra insulated neutral conductor is required for the metallic return when compared to the bipole with ground return.

Fig. 5. Bipole HVDC link with metallic return.

3. Comparison of HVDC Links

Table 1 presents the comparison of different HVDC link configurations.

References

Connect with us via mohanbe.m@gmail.com